Model No.: I3D40K

 
I3D40K 3/1 Phase 40Kva 380/220Vac DSP Low Frequency Online Industrial

 

I3D40K 3/1 Phase 40Kva 380/220Vac DSP Low Frequency Online Industrial UPS 

 

Application:

Networking, for data centers, network centers, calling centers, emergency publics, banks, service counters, telecom cabinets, industrial production lines, critical machines, medical facilities, as the list goes on and on.

 

Functions & Features

1. On-line UPS

2. DSP system

3. IGBT technology

4. CPU control

5. LCD display

6. Double conversion  

 

About Shipping:

1. We use very thick plywood case with pallet base to pack our machines.

2. We only hand our goods to authentic DHL, FedEx, UPS or TNT for shipping.

3. Please select the applicable shipping agent in our shipping rate chart. The rates to each country are very accurate.

4. The production time is about 2 weeks.( When some models we have stock,we can ship out within 3 days. The shipping time is about 5 days to 10 days which also depends on the customs clearance in your country.

 

bigPhoto
 Mr. Lisa Zhao

Tel: 86-755-83265608
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Company Info

Shenzhen Zhongyuan Chuangda Technology Co., Ltd [China (Mainland)]


Business Type:Manufacturer
City: Shenzhen
Province/State: Guangdong
Country/Region: China (Mainland)

You May Like:

Product (118)

Input voltage

Rated voltage

380VAC

Line voltage

Phase

3 + N +P E(protective earth)

 

Turn on voltage range

380VAC±25%

Line voltage

Bypass voltage range

220VAC±25%

Phase voltage

Could be adjusted by software.

Bypass low loss

165VAC

Bypass low comeback

Low loss +10VAC

Bypass high loss

275VAC

Bypass high comeback

High loss-10VAC

Line low loss/comeback

(165±5) VAC /(180±5) VAC

 

Line high loss/comeback

(275±5)VAC/(260±5)VAC

 

Input frequency

Rated frequency

50Hz

Could be adjusted by software.

Frequency low loss

(40~49)±0.2Hz(default:46Hz)

Frequency low comeback

Frequency low loss + 0.5Hz

Frequency high loss

(51~60)±0.2Hz(default:54Hz)

Frequency high comeback

Frequency high loss - 0.5Hz

Input power factor

Input power factor

0.7

220VAC,full R load

Generator

Support generator input

Generator rating≥2*UPS rating

Input current

Rated current

95A

 

Input protection

Rated protection

100A